Slide 6

Combi Module I/O

The CombiModule I/O is a control unit for our signalling and evacuation products. The unit is being managed by I/O contacts. The I/O entrances and exits are defined by the National Dutch Tunnel Standard (LTS).

The unit contains multiple outputs such as:

  • 2x CV = 2x constant voltage, direct control of low power LEDs at 24 VDC
  • 2x CC = 2x constant current, direct control of high power LEDs up to 500 mA
  • 2x AU = audio total 2 x 25

Important advantages

  • Complies with LTS v1.2
  • One central unit for controlling multiple products
  • Cost-saving: one module controls multiple products
  • Simple control via I/O ports
  • Compact solution: 162 x 90 x 63 (L x W x H)
  • Easy to install and interchangeable due to the DIN rail
  • Internally or externally placeable in the fixture

Electrical properties

  • 24 VDC input voltage
  • Maximum power consumption = 120W
    • Pout, max 2x CV = 45W (V, out: 24 VDC)
    • Pout, max CC = 20W (C, out: 350 mA)
    • Pout, max AU = 50W (2 x 25W)
  • 7 x I/O input, 5 x I/O output
  • Surrounding temperature can differ form -25°C to +55°C
  • Technical lifespan 10,000 burning hours at Tq = 25°C

Mechanical properties

  • Connection screw connection, max. 2.5 mm2 diameter cable
  • Housing is DIN-rail
  • Equipped with SD card holder

Certificates

  • Product certification EN 1090-1
  • Managementsysteem certificate ISO 9001
  • Eurocodes
  • VCA+
  • MVO Nederland Partner
  • Cradle to Cradle
  • CO2-Prestatieladder
  • CE